AT-8000 - AMPROBE

Código: Amprobe-AT-8000 Marca:

Product Highlights

The AT-8000 is the first CAT IV 600 V Advanced Wire Tracer Series designed to protect electricians from the most dangerous level of transient overvoltage spikes up to 8,000 V known to occur in industrial environments. The Receiver is equipped with patented Smart Sensor™ technology, which finds and displays the location and orientation of Energized wires in walls, floors and ceilings on the large color TFT LCD screen.

The Scan and Locate feature clearly identifies the single correct breaker or fuse, eliminating the confusion from multiple false positive readings common in older technology tracing tools. Embedded help screens make set-up easy and error free for novice users and experts alike.

Featuring three power modes “high”, “low”, and “loop” and two output frequencies (6 kHz and 33 kHz), the AT-8000-T Transmitter incorporates the best technologies available for optimal wire tracing and breaker identification on both energized and de-energized circuits. The AT-8000-T automatically sets the signal based on detected voltage and prompts the user to set the power level based on the application, delivering consistently accurate results.

The AT-8030 kit includes the CT-400 Signal Clamp for inducing signal into wires without access to bare conductors.

Specifications

Features AT-8000-R Receiver AT-8000-T Transmitter CT-400 Signal Clamp
Display size LCD 3.5 in (89 mm) LEDs N/A
Display dimensions (W x H) 2.76 x 2.07 in (70 x 52 mm) N/A N/A
Display Resolution 320 x 240 N/A N/A
Display type Color TFT LCD LEDs N/A
Display color Yes Operating mode LEDs: red
Battery status LEDs: green, yellow, red
N/A
Booting time 30 sec < 2 sec N/A
Backlight Yes N/A N/A
Operating temperature -4 °F to 122 °F (-17.77 °C to 49 °C) -4 °F to 122 °F (-20 °C to 50 °C) 32 °F to 122 °F (0 °C to 50 °C)
Operating humidity 45%: -4 °F to <50 °F (-20 °C to <10 °C)
95%: 50 °F to <86 °F (10 °C to <30 °C)
75%: 86 °F to <104 °F (30 °C to <40 °C)
45%: 104 °F to 122 °F (40 °C to 50 °C)
45%: -4 °F to <50 °F (-20 °C to <10 °C)
95%: 50 °F to <86 °F (10 °C to <30 °C)
75%: 86 °F to <104 °F (30 °C to <40 °C)
45%: 104 °F to 122 °F (40 °C to 50 °C)
95%: 50 °F to <86 °F (10 °C to <30 °C)
75%: 86 °F to <104 °F (30 °C to <40 °C)
45%: 104 °F to <122 °F (40 °C to <50 °C)
Storage temperature and humidity -4 °F to 158 °F (-20 °C to 70 °C), <95% RH -4 °F to 158 °F (-20 °C to 70 °C), <95% RH -4 °F to 140 °F (-20 °C to 60 °C), <95% RH
Operating altitude 0 to 6561 ft (2000 m)
Transient protection N/A 8.00 kV (1.2/50μS surge) N/A
Pollution degree 2
IP rating IP 52 IP 40
Drop test 3.28 ft (1 m)
Power supply 4 x AA (alkaline) 8 x AA (alkaline) N/A
Power consumption (typical) 4xAA battery: 2W Hi mode: 70 mA
Loop mode with Clamp: 90 mA
Consumption without signal transmission: 10 mA
N/A
Battery life Approx. 9 h Hi mode: approx. 25 h
Loop mode: approx. 18 h
N/A
Low battery indication Yes N/A
Fuse N/A 1.6 A, 700 V, fast-acting,
Ø 6x32mm
N/A
Maximum conductor size N/A N/A 1.26 in (32 mm)
Dimensions (L x W x H) Approx. 10.92 x 4.43 x 2.55 in
(27.75 x 11.25 x 6.5 cm)
Approx. 7.2 x 3.66 x 1.97 in
(18.3 x 9.3 x 5 cm)
Approx. 5.9 x 2.75 x 1.18 in
(15 x 7 x 3 cm)
Weight Approx. 1.20 lb (0.544 kg) Approx. 1.25 lb (0.57 kg) Approx. 0.25 lb (0.114 kg)

Refer to user manual for accessory specifications